This study investigates the seismic response of a G+8 reinforced concrete (RC) building with vertical stiffness irregularity and compares four structural modification strategies. Five configurations are considered: the general building, building with shear walls, building with steel bracings, building with double-storey height, and building with modified member properties. The models are analysed in STAAD.Pro using the Response Spectrum Method under the seismic parameters reported in the project presentation. The response is compared using maximum storey displacement, ground-storey shear, maximum/reference bending moment, fundamental time period and fundamental frequency. The general model records a maximum displacement of 5.670 mm and ground-storey shear of 61.562 kN. Modified member properties produce the lowest reported maximum displacement of 3.487 mm, a reduction of 38.50% from the general model. The double-storey-height configuration records the lowest ground-storey shear of 49.250 kN, a reduction of approximately 20%. The braced configuration has the shortest fundamental time period of 0.590 s and the highest fundamental frequency of 1.695 Hz. The results demonstrate that the examined modifications influence both lateral response and dynamic characteristics. The findings are limited to the model properties, loading assumptions and analysis results documented in the source presentation.
Introduction
Earthquake-induced damage in buildings is often caused by vertical irregularities in mass, stiffness, and geometry. Soft-storey structures are particularly vulnerable because their reduced stiffness can lead to excessive lateral displacement and concentration of seismic forces. This study investigates the seismic behaviour of a G+8 reinforced concrete (RC) building and evaluates the effectiveness of different structural modifications in improving its earthquake resistance.
The study uses STAAD.Pro to model and analyse five structural configurations: a general G+8 building, a building with shear walls, a building with steel bracing, a building with double-storey height, and a building with modified member properties. Response Spectrum Analysis is performed to evaluate important structural parameters, including storey displacement, storey shear, bending moment, fundamental time period, and frequency, considering relevant Indian seismic design codes.
The results indicate that the modified-member configuration achieves the lowest displacement of 3.487 mm, representing a 38.50% reduction compared with the general building model. The steel-bracing configuration also provides significant improvement, reducing displacement to 3.631 mm while achieving the shortest fundamental time period of 0.590 seconds. The double-storey-height configuration records the lowest storey shear of 49.250 kN, while the modified-member configuration produces the highest reported bending moment of 29.458 kN-m.
Conclusion
1) The G+8 RC building was evaluated using the Response Spectrum Method in STAAD.Pro under the seismic parameters reported in the project presentation.
2) The general building recorded a maximum displacement of 5.670 mm and ground-storey shear of 61.562 kN.
3) Modified member properties produced the lowest reported maximum displacement of 3.487 mm, corresponding to a 38.50% reduction relative to the general model.
4) The double-storey-height configuration produced the lowest reported ground-storey shear of 49.250 kN, corresponding to an approximately 20% reduction.
5) The bracing configuration produced the shortest fundamental time period of 0.590 s and the highest reported fundamental frequency of 1.695 Hz.
6) Bending-moment changes were comparatively modest and varied with the redistribution of lateral forces among the structural members.
7) The results show that changes to the lateral-load-resisting system, building geometry and member properties influence both lateral response measures and dynamic characteristics.
References
[1] Bureau of Indian Standards, IS 875 (Part 1):1987, Code of Practice for Design Loads (Other than Earthquake) for Buildings and Structures—Dead Loads, New Delhi, 1987.
[2] Bureau of Indian Standards, IS 875 (Part 2):1987, Code of Practice for Design Loads—Imposed Loads, New Delhi, 1987.
[3] Bureau of Indian Standards, IS 875 (Part 3):1987, Code of Practice for Design Loads (Other than Earthquake) for Buildings and Structures—Wind Loads, New Delhi, 1987.
[4] Bureau of Indian Standards, IS 456:2000, Plain and Reinforced Concrete—Code of Practice, New Delhi, 2000.
[5] I. H. Cagatay, C. Beklen and K. M. Mosalam, “Investigation of short column effect of RC buildings: Failure and prevention,” Computers and Concrete, vol. 7, no. 6, pp. 523–532, 2010.
[6] K. Gowda and S. Tajoddeen, “Seismic analysis of multistorey building with floating columns,” 2014. [Publication details to be completed from the original source.]
[7] H. Bansal and Gagandeep, “Seismic analysis and design of vertically irregular RC building frames,” International Journal of Science and Research, vol. 3, no. 8, 2012. [Page details to be verified.]
[8] Federal Emergency Management Agency, NEHRP Recommended Seismic Provisions for New Buildings and Other Structures, FEMA P-1050-1, 2015.
[9] A. S. Bhosale, R. Davis and P. Sarkar, “Seismic safety of vertically irregular buildings: Performance of existing indicators,” Journal of Architectural Engineering, vol. 24, no. 3, art. 04018013, 2018.
[10] Bureau of Indian Standards, IS 1893 (Part 1):2016, Criteria for Earthquake Resistant Design of Structures—General Provisions and Buildings, New Delhi, 2016.
[11] Bureau of Indian Standards, IS 875 (Part 3):2015, Design Loads (Other than Earthquake) for Buildings and Structures—Wind Loads, New Delhi, 2015.